T-10 Maintenance Item
Array [20]
Option:
Function:
[12]
System health check
[13]
Warranty
[20]
Maintenance Text 0
[21]
Maintenance Text 1
[22]
Maintenance Text 2
[23]
Maintenance Text 3
[24]
Maintenance Text 4
[25]
Maintenance Text 5
T-11 Maintenance Action
Array [20]
Option:
Function:
Select the action to be associated with
the preventive maintenance event.
[1]
*
Lubricate
[2]
Clean
[3]
Replace
[4]
Inspect/Check
[5]
Overhaul
[6]
Renew
[7]
Check
[20]
Maintenance Text 0
[21]
Maintenance Text 1
[22]
Maintenance Text 2
[23]
Maintenance Text 3
[24]
Maintenance Text 4
[25]
Maintenance Text 5
T-12 Maintenance Time Base
Array [20]
Option:
Function:
Select the time base to be associated with the
preventive maintenance event.
[0]
*
Disabled
Disables the preventive maintenance event.
[1]
Running
Hours
The number of hours the motor has run.
Running hours are not reset at power-on.
Specify the maintenance time interval in
parameter T-13 Maintenance Time Interval
.
[2]
Operating
Hours
The number of hours the frequency converter
has run. Operating hours are not reset at
power-on. Specify the maintenance time
parameter T-13 Maintenance Time
[3]
Date &
Time
Uses the internal clock. Specify the date and
time of the next maintenance occurrence in
parameter T-14 Maintenance Date and Time
.
T-13 Maintenance Time Interval
Array [20]
Range:
Function:
1
h
*
[1 -
2147483647
h]
Set the interval associated with the current
preventive maintenance event. This
parameter is only used if
[1] Running Hours
or
[2] Operating Hours
is selected in
parameter T-12 Maintenance Time Base
. The
timer is reset from
Example
A preventive maintenance event is set up
Monday at 8:00.
is
[2] Operating hours
and
parameter T-13 Maintenance Time Interval
is 7
x 24 hours=168 hours. Next maintenance
event is indicated the following Monday at
8:00. If this maintenance event is not reset
until Tuesday at 9:00, the next occurrence is
the following Tuesday at 9:00.
T-14 Maintenance Date and Time
Array [20]
Range:
Function:
0
*
[0 -
0]
Set the date and time for next maintenance
occurrence if the preventive maintenance event is
based on date/time. Date format depends on the
while the
time format depends on the setting in
NOTICE
The frequency converter has no back-up of
the clock function and the set date/time is
reset to default (2000-01-01 00:00) after a
power-down. In
, it
is possible to programme a warning if the
clock has not been set properly, for example
after a power-down.
Set the time at least 1 hour later than actual
time!
NOTICE
When mounting an Analog I/O option option
card, a battery back-up of the date and time
is included.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
147