K-15 Readout: Actual Set-up
Range:
Function:
0
*
[0 - 255]
3.1.3 K-2# Keypad Display
Define the variables displayed in the keypad.
[0]
*
None
No display value selected
[537]
Display Text 1
Enables an individual text string to be
written, for display in the keypad or to
be read via serial communication.
[538]
Display Text 2
Enables an individual text string to be
written, for display in the keypad or to
be read via serial communication.
[539]
Display Text 3
Enables an individual text string to be
written, for display in the keypad or to
be read via serial communication.
[589]
Date and Time
Readout
Displays the current date and time.
[953]
Profibus
Warning Word
Displays Profibus communication
warnings.
[2205] Readout
Transmit Error
Counter
View the number of CAN control
transmission errors since the last power-
up.
[2206] Readout
Receive Error
Counter
View the number of CAN control receipt
errors since the last power-up.
[2207] Readout Bus
Off
Counter
View the number of Bus Off events
since the last power-up.
[2213] Warning
Parameter
View a DeviceNet-specific warning word.
One separate bit is assigned to every
warning.
[1501] Running Hours
View the number of running hours of
the motor.
[1502] kWh Counter
View the mains power consumption in
kWh.
[1200] Control Word
View the Control Word sent from the
frequency converter via the serial
communication port in hex code.
[1201] Reference [Unit] Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow-down) in selected unit.
[1202] Reference [%]
Total reference (sum of digital/analog/
preset/bus/freeze ref./catch up and
slow-down) in percent.
[1203] Status Word
Present status word
[1205] Main Actual
Value [%]
View the two-byte word sent with the
Status word to the bus Master reporting
the Main Actual Value.
[1209] Custom
Readout
View the user-defined readouts as
defined in
parameter K-32 Max Value of Custom
[1210] Power [kW]
Actual power consumed by the motor
in kW.
[1211] Power [hp]
Actual power consumed by the motor
in HP.
[1212] Motor Rated
Voltage
Voltage supplied to the motor.
[1213] Frequency
Motor frequency, i.e. the output
frequency from the frequency converter
in Hz
[1214] Motor Current
Phase current of the motor measured as
effective value.
[1215] Frequency [%]
Motor frequency, i.e. the output
frequency from the frequency converter
in percent.
[1216] Torque [Nm]
Present motor load as a percentage of
the rated motor torque.
[1217] Speed [RPM]
Motor speed reference. Actual speed
will depend on slip compensation being
parameter P-09 Slip Compensation
). If not
used, actual speed will be the value
read in the display minus motor slip.
[1218] Motor Thermal
Thermal load on the motor, calculated
by the Electronic Thermal Overload
function. See also parameter group H-9#
Motor Temperature.
[1222] Torque [%]
Shows the actual torque produced, in
percentage.
[1230] DC Link Voltage Intermediate circuit voltage in the
frequency converter.
[1232] Brake Energy /s
Present brake power transferred to an
external brake resistor. Stated as an
instantaneous value.
[1233] Brake Energy /2
min
Brake power transferred to an external
brake resistor. The mean power is
calculated continuously for the most
recent 120 seconds.
[1234] Heatsink Temp.
Present heat sink temperature of the
frequency converter. The cut-out limit is
95
±
5
°
C; cutting back in occurs at 70
±
5
°
C.
[1235] Drive Thermal
Percentage load of the inverters.
[1236] Drive Nominal
Current
Nominal current of the frequency
converter.
[1237] Drive Max.
Current
Maximum current of the frequency
converter.
[1238] Logic Controller
State
State of the event executed by the
control.
[1239] Control Card
Temp.
Temperature of the control card.
[1250] External
Reference
Sum of the external reference as a
percentage, i.e. the sum of analog/
pulse/bus.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
27