LC-52 Logic Controller Action
Array [20]
Option:
Function:
[90]
Set ECB Bypass
Mode
[91]
Set ECB Drive
Mode
[100] Reset Alarms
3.25.7 LC-9#
LC-90 Alert Trigger
Array [10]
Select the event that triggers the user-defined action and
message.
Option:
Function:
[0]
*
False
[1]
True
[18]
Reversing
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
Logic Controller Time-out 0
[31]
Logic Controller Time-out 1
[32]
Logic Controller Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
Logic Controller Time-out 3
[71]
Logic Controller Time-out 4
[72]
Logic Controller Time-out 5
[73]
Logic Controller Time-out 6
[74]
Logic Controller Time-out 7
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
LC-91 Alert Action
Array [10]
Select the action that the frequency converter performs when
occurs.
Option:
Function:
[0]
*
Info
[1]
Warning
[2]
Freeze output
[3]
Freeze output & warn
[4]
Stop
[5]
Stop & warning
[6]
Jogging
[7]
Jogging & warning
[8]
Max speed
[9]
Max speed & warn
[10]
Stop and trip
[11]
Stop and trip w manual
reset
[12]
Trip
[13]
Trip w manual reset
[14]
Trip Lock
LC-92 Alert Text
Array [10]
Range:
Function:
0
*
[0 - 20] Enter the text that the frequency converter shows
in the display when the event defined in
parameter 13-90 Alert Trigger
occurs.
LC-97 Alert Alarm Word
Range:
Function:
0
*
[0 - 4294967295] Shows the alarm word of a user-defined
alarm in hex code.
LC-98 Alert Warning Word
Range:
Function:
0
*
[0 - 4294967295] Shows the warning word of a user-
defined alarm in hex code.
LC-99 Alert Status Word
Range:
Function:
0
*
[0 - 4294967295] Shows the status word of a user-defined
alarm in hex code.