7-40
7.
Fuji
Electric
7.2.12 FRENIC-Mini (MODBUS RTU)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
*1
When no parity setting is made, “2 bits” is set for stop bit.
When a parity setting (even or odd) is made, “1 bit” is set for stop bit.
Inverter
Set communication parameters.
Be sure to match the settings to those made on the [Communication Setting] tab window of the editor. (Underlined setting:
default)
*1
Select “Modbud RTU” for the communication protocol on the inverter when connecting with the S8.
*2
When “0” is specified for y99 (support link function), command from function code H30 is valid for the frequency setting and operation
command.
Item
Setting
Remarks
Connection Mode
1 : 1 / 1 : n / Multi-link2
Signal Level
RS-232C / RS-422/485
Baud Rate
4800 / 9600 / 19200 bps
Data Length
8 bits
Do not change the default setting
because the setting on the inverter
cannot be changed.
Stop bit
1 / 2 bits
*1
Parity
None / Odd / Even
Target Port No.
1 to 31
Function
Code
Item
Setting
Example
y01
Station address
1 to 31
1
y04
Baud rate
1: 4800 bps
2: 9600 bps
3: 19200 bps
3
y06
Parity bit
0: None
1: Even
2: Odd
0
y07
Stop bit
For Modbus RTU communication, the stop bit setting is
automatically made according to the parity bit setting.
When no parity setting is made, “2 bits” is set for stop bit.
When a parity setting (even or odd) is made, “1 bit” is set
for stop bit.
-
y10
Communication
protocol
*1
0: Modbus RTU
1: SX (loader) protocol
2: FGI-bus
0
y99
Support link function
0
H30
Link function
*2
3
Frequency
Operation Command
0
Function code H30
Function code H30
1
Commanded from RS-485
Function code H30
2
Function code H30
Commanded from RS-485
3
Commanded from RS-485
Commanded from RS-485
Frequency
Operation Command
0
Inverter
Inverter
1
RS-485 communication
Inverter
2
Inverter
RS-485 communication
3
RS-485 communication
RS-485 communication
Summary of Contents for Monitouch S8 series
Page 1: ...Connection Manual...
Page 3: ......
Page 5: ......
Page 17: ......
Page 19: ......
Page 43: ...1 24 1 Overview...
Page 44: ...2 1 PLC Connection 2 ALLEN BRADLEY...
Page 45: ......
Page 56: ...3 1 PLC Connection 3 Automation Direct...
Page 57: ......
Page 66: ...4 EATON Cutler Hammer 4 1 PLC Connection...
Page 67: ......
Page 71: ...4 4 4 EATON Cutler Hammer Please use this page freely...
Page 72: ...5 FANUC 5 1 PLC Connection...
Page 73: ......
Page 78: ...6 FATEK AUTOMATION 6 1 PLC Connection...
Page 79: ......
Page 84: ...7 Fuji Electric 7 1 PLC Connection 7 2 Temperature Controller Servo Inverter Connection...
Page 85: ......
Page 158: ...8 IAI 8 1 Temperature Controller Servo Inverter Connection...
Page 159: ......
Page 173: ...8 14 8 IAI Please use this page freely...
Page 174: ...9 KEYENCE 9 1 PLC Connection...
Page 175: ......
Page 186: ...10 LS 10 1 PLC Connection...
Page 187: ......
Page 197: ......
Page 223: ...11 26 11 MITSUBISHI ELECTRIC Please use this page freely...
Page 224: ...12 OMRON 12 1 PLC Connection 12 2 Temperature Controller Servo Inverter Connection...
Page 225: ......
Page 244: ...13 Panasonic Electric Works 13 1 PLC Connection...
Page 245: ......
Page 253: ...13 8 13 Panasonic Electric Works Please use this page freely...
Page 254: ...14 RKC 14 1 Temperature Controller Servo Inverter Connection...
Page 255: ......
Page 264: ...15 SAIA 15 1 PLC Connection...
Page 265: ......
Page 269: ...15 4 15 SAIA Please use this page freely...
Page 270: ...16 1 PLC Connection 16 Siemens...
Page 271: ......
Page 276: ...17 1 Temperature Controller Servo Inverter Connection 17 Yamatake...
Page 277: ......
Page 285: ...17 8 17 Yamatake Please use this page freely...
Page 286: ...18 Yaskawa Electric 18 1 PLC Connection...
Page 287: ......
Page 295: ...18 8 18 Yaskawa Electric Please use this page freely...
Page 296: ...19 1 PLC Connection 19 2 Temperature Controller Servo Inverter Connection 19 Yokogawa Electric...
Page 297: ......
Page 307: ...19 10 19 Yokogawa Electric Please use this page freely...
Page 308: ...20 1 PLC Connection 20 MODBUS...
Page 309: ......
Page 314: ...21 1 Barcode Reader Connection 21 Barcode Reader...
Page 315: ......
Page 320: ...22 1 V Link 22 2 Modbus RTU Slave Communication 22 Slave Communication Function...
Page 321: ......
Page 333: ...22 12 22 Slave Communication Function Please use this page freely...
Page 335: ......
Page 367: ...23 32 23 Universal Serial Communication Please use this page freely...
Page 369: ......
Page 403: ...App4 6 Please use this page freely...