![Fischer Panda Panda PMS-HD 12-4KU Manual Download Page 57](http://html1.mh-extra.com/html/fischer-panda/panda-pms-hd-12-4ku/panda-pms-hd-12-4ku_manual_2294313057.webp)
Generator Failure
Seite 57 Panda PMS 8.000 NE - 42 NE Manual.R04 - Kapitel B: Generator Failure
8.7.08
This period can be reduced by pushing the button on the front of the generator. The generator
can be started by means of the remote control as long as the button is depressed. The switch/
button bypasses any faults allowing the generator to run.
Before depressing the button, a manual check of the oil dip stick must be carried out to determine
whether the generator has sufficient oil, as it is possible that the oil pressure switch causes the
generator to cut out. If it has been ascertained that the reason for the motor cutting out is over-
heating and not lack of oil, the generator can be run for several minutes without load, so that the
motor is cooled by the circulating coolant.
BEWARE:
If the temperature is the reason for the generator cutting out when it is running under load, then
an immediate check must be made to determine the cause. It could be a fault with the cooling
system, one of the fans, the air-intake or a fault with the external cooling system.
Continual use of the starter-failure bypass switch should be avoided, while the generator cuts out
during operation.
The generator must always run without load for several minutes before being switched off, so that
temperature compensation occurs. Heat accumulation can cause the generator to overheat, even
after it has been switched off.
Should the overheating alarm be set off, caused by heat accumulation, after the generator has
been switched off, then this can also be bypassed using the switch.
Damage to starter motor
The starter is fitted with a free wheel or axial rotating spring cog, which prevents the starter being
driven externally by means of the motor. The free wheel will be heavily worn, if the starter still
operates, thereby causing damage to the springs, roller bearings or cog teeth. This could lead to
complete destruction of the starter.
It is important that every person who operates the generator is informed of this situation.
This is practically the only handling error that can be made on board that can lead to fatal
consequences for both generator and operator.
B.6.3 Troubleshooting Table
For Troubleshooting see Table “Troubleshooting” on Page I.