General operation
Page 134 Panel Generator Control P6+ RE0703_Kunde_eng.R02 - Chapter A: General operation
8.7.08
J202
1-2
Water leak-input / Replace air filter, for contact, which opens in case of error (2)
2-3
X
Water leak-input / Replace air filter, for contact, which closes in case of error (2)
J203
1-2
X
Oil-Press-input, for contact, which opens in case of error (2)
2-3
Oil-Press-input, for contact, which closes in case of error (2)
J204
1-2
X
AC-Fault-input / Fuel level, for contact, which opens in case of error (2)
2-3
AC-Fault-input / Fuel level, for contact, which closes in case of error (2)
J205
1-2
X
T-Winding-input, for contact, which opens in case of error (2)
2-3
T-Winding-input, for contact, which closes in case of error (2)
J206
1-2
X
Input Water leak has red LED and switches off
2-3
Input Water leak has yellow LED and does not switch off
J207
1-2
X
Input AC-Fault has red LED and switches off
2-3
Input AC-Fault has yellow LED and does not switch off
J208
1-2
X
DC-Control-Signal (-) = OK alternator
2-3
DC-Control-Signal (+) = OK three-phase alternator
J209
1-2
X
DC-Control-Signal (-) = OK alternator
2-3
DC-Control-Signal (+) = OK three-phase alternator
J210
closed
Input AC-Fault has Pull-Up-current
≥
10mA
open
X
Input AC-Fault has Pull-Up-current
≥
2,5mA
The solder jumpers are marked on the printed circuit board (with jumper no. and at three-part solder jumper with
soldering surface no.)
(1): Equivalent resistance for load control lamp e.g. for use with three-phase alternator also integrated automatic
controller of Bosch. The resistance value is 68
Ω
3W, i.e. only for 12V.
(2): A closed contact switches the appropriate input to GND.