![Fischer Panda Panda PMS-HD 12-4KU Manual Download Page 103](http://html1.mh-extra.com/html/fischer-panda/panda-pms-hd-12-4ku/panda-pms-hd-12-4ku_manual_2294313103.webp)
Installation Instructions
8.7.08
Panda PMS 8.000 NE - 42 NE Manual.R04 - Capture D: Installation Instructions Seite 103
D.8.5 Jump Start at High Starting Current (Booster)
Additionally, the automatic start booster is located on the circuit control board. The starting cur-
rent is increased by connecting a second group of capacitors (C2), if the voltage drops below a
pre-set voltage. The starting current can be increased by 300% for a short period by combining
both components voltage/speed control and ASB Start booster.
D.9 Insulation Test
ATTENTION: Once the electrical system installation is complete, a
ground insulation test must be performed as follows:
1.) Switch off all on-board electrical devices.
2.) Start the generator.
3.) Measure the AC-voltage with a voltmeter (adjust to Volt/AC) between
a) generator housing and AC-Control box
b) generator housing and ground.
The measured voltage must not exceed 50mV (millivolts).
4. Once the safety systems have been installed, they must be checked. If a Leakage Current
Relay has been installed, it also has to be tested, in order to ensure that it functions properly.
The individual phrases must be checked against each other, and between phase and ground,
(the single phase or 4th phase also needs to be checked in this fashion).
5. If the generator is protected by a ground connection, then ALL electrical devices must also be
connected to this "common" ground (usually ground contacts are attached to the devices'
metallic housings).
The electrical system installation must also comply with the hook-up requirements of the shore
current grid. Generally a leakage current relay is sufficient for safe electrical operation; however,
this must be confirmed by the electrical safety standard in the region where the system is atta-
ched to a main land power grid. The relay has to meet the required safety standard regulations.
Checking the Electrical Connections
There is always the possibility that circuits have been rerouted/changed or individual components
have not been not been correctly laid out on the circuit diagrams.
The installation electrician should therefore check and label all electrical connections to ensure
that they correspond to the main circuit diagram. The inspection and correct labelling is especially
critical for terminals L1/ L2/L3/L1'/N (for the 230 V - 50 Hz model) and for terminals L1/L2/L3/N
&1/ 2/ 4 for the 60 Hz (120 V) models. The electrician is therefore obliged, before installation to
check whether the generator is earth-free. As long as this test has not been carried out all other
components for electrical installation must be removed. Once the system has been installed and
inspected, this test should also be performed with all electrical devices (i.e. voltage check bet-
ween common and metallic housings) while the generator is running.