General operation
8.7.08
Panel Generator Control P6+ RE0703_Kunde_eng .R02 - Chapter A: General operation Page 137
3. Press button „start“ (start engine).
LED for "start“ = green.
The electric starter may only be used for a maximum of 20
seconds. Thereafter, a pause of at least, 60 seconds is required. If
the genset does not immediately start, then the fuel intake should
be checked to ensure it is flowing freely. (For temperatures below -
8°C check whether there is winter fuel)
4. Switch on load.
The load should only be switched on if the generator voltage is within the permissible range. Parallel connection of several loads
should be avoided, especially if there are loads with electric motors, such as air-conditioning units in the system. In this case, the load
must be connected Step by Step.
A.5.2 Stopping the generator
1. Switch off load.
2. Recommendation: With turbo engines and during load more than highly 70% of the rated output, stabilize
generator temperature at least 5 minutes with load switched off.
At higher ambient temperatures (more than 25°C) the generator should always run for at least 5 minutes without load, before it is swit-
ched off, regardless of the load.
3. Press button „off“ (switch off).
LED for "on“ = off.
NOTE: Never switch off the battery until the generator has stopped, if nec-
essary close fuel valve!
A.5.1 Starting the generator