General operation
8.7.08
Panel Generator Control P6+ RE0703_Kunde_eng .R02 - Chapter A: General operation Page 129
Notes:
1. Power rating of the output: max. 0,5A in continuous operation and briefly 1,0A.
2. The supply of all output currents may not exceed (less 0,2A power consumption) the rated current of the safety
device of the control panel.
3. The output has a free wheeling diode, which short circuits negative voltages (related to GND).
4. The output has a Z-diode, which prevents a supply of positive voltage (related to GND) into the output.
A.3.2 Function of the jumpers
Jumper
Status
Description
J1
closed
during operation of the start button heat is along-operated
open
Function deactivated
J3
1-2
Dynamo excitation resistor 68R is switched on with Fuel-Pump (1)
2-3
Dynamo excitation resistor 68R is switched on with Panel-ON (1)
open
Dynamo excitation resistor is deactivated
J101
closed
12V - operation
open
24V - operation (optional)
J201
1-2
T-Engine-input, for contact, which opens in case of error (2)
2-3
T-Engine-input, for contact, which closes in case of error (2)
J202
1-2
Water leak-input / Replace air filter, for contact, which opens in case of error (2)
2-3
Water leak-input / Replace air filter, for contact, which closes in case of error (2)
J203
1-2
Oil-Press-input, for contact, which opens in case of error (2)
2-3
Oil-Press-input, for contact, which closes in case of error (2)
J204
1-2
AC-Fault-input / Fuel level, for contact, which opens in case of error (2)
2-3
AC-Fault-input / Fuel level, for contact, which closes in case of error (2)
J205
1-2
T-Winding-input, for contact, which opens in case of error (2)
2-3
T-Winding-input, for contact, which closes in case of error (2)
J206
1-2
Input Water leak has red LED and switches off
2-3
Input Water leak has yellow LED and does not switch off
J207
1-2
Input AC-Fault has red LED and switches off
2-3
Input AC-Fault has yellow LED and does not switch off
J208
1-2
DC-Control-Signal (-) = OK alternator
2-3
DC-Control-Signal (+) = OK three-phase alternator
J209
1-2
DC-Control-Signal (-) = OK alternator
2-3
DC-Control-Signal (+) = OK three-phase alternator
J210
closed
Input AC-Fault has Pull-Up-current
≥
10mA
open
Input AC-Fault has Pull-Up-current
≥
2,5mA
Fig. A.3.2-1: Function of the solder jumper