Festo — MSE6-C2M — 2022-08b
Parameterisation
83
Module parameter: behaviour after SCS
Function number
4828 + m * 64 + 27
m = module number 0
Description
The parameter determines whether the voltage remains switched off after a
short-circuit/overload of the sensor power supply 24 V DC U
SEN
or is switched
on again automatically.
Bit
Bit 6
Values
0 = leave switched off
1 = switch on again, default
Comment
If the setting is leave switched off, Power Off/On is required to restore the
power.
–
Check which setting is required for the safe operation of the system
Tab. 70: Behaviour after SCS module parameter
Module parameter: behaviour after SCO
Function number
4828 + m * 64 + 27
m = module number 0
Description
The parameter determines whether the corresponding voltage remains switched
off or is switched on again automatically after a short-circuit/overload of the
electrical outputs in this module.
Bit
Bit 7
Values
0 = leave switched off, default
1 = switch on again
Comment
If the setting is leave switched off, Power Off/On or Reset/Setting of the corre-
sponding output is required to restore power.
–
Check which setting is required for the safe operation of the system.
Tab. 71: Behaviour after SCO module parameter
Module parameter: Q_low-Timer reset selection
Function number
4828 + m * 64 + 28
m = module number 0
Description
The parameter defines the signal source for resetting the Q_low-Timers when
automatic pressure regulation and blocking functions are activated.
Bit
Bit 0, 1
Bit
1 0
Value
Meaning
0 0
0 = Am.0.2, default
Output Am.0.2
0 1
1 = DI0
Electrical input 0