38
Festo — MSE6-C2M — 2022-08b
Functions
Input data, shut-off function
Data bit B0 has the following values:
–
0 = shut-off valve open, pressurisation status
–
1 = shut-off valve closed, blocking state
Data bits B4, B5 indicate the status of the Q_low-Timers and have the following values:
–
0 = RESET: Q_low-Timernot started
–
1 = RUN: Q_low-Timer running
–
2 = UP: Q_low-Timer expired
Data bits B8 … B11 signal the current function status and have the following values:
–
0 = USER_RISE: pressure increase until user-set setpoint pressure is reached, USER mode
–
1 = USER_PON: pressure regulation to set power-on setpoint pressure, USER mode
–
2 = USER_MIN: pressure regulation to minimum setpoint pressure = 2.5 bar, USER mode
–
3 = USER_REGOFF: electronic pressure regulation deactivated, USER mode
–
4 = USER_VAR: pressure regulation to set setpoint pressure according to Am.2, USER mode
–
5 = USER_SHUTOFF: module in blocking state, USER mode
–
7 = OFF_24VA: no load voltage supply, pressure control function and blocking function not active,
USER/AUTO mode
–
8 = AUTO_NORMAL: pressure regulation at parameterised setpoint pressure auto normal, AUTO
mode
–
9 = AUTO_WAIT: pressure regulation at parameterised setpoint pressure auto normal during an
underrun of the parameter value auto-controller flow rate limit value, Q_low-Timer running, AUTO
mode
–
10 = AUTO_HOLD: pressure control to the configured auto normal setpoint pressure, Q_low-Timer
expired, automatic pressure control function and blocking function not activated, AUTO mode
–
11 = AUTO_SHUTOFF: module in lockout state, Q_low-Timer expired, automatic pressure control
function and lockout function activated, AUTO mode
–
12 = AUTO_STANDBY: pressure regulation to parameterised setpoint pressure auto standby, AUTO
mode
–
13 = AUTO_RISE: pressure increase up to the configured setpoint pressure auto normal, AUTO
mode
Input data of pressure measurement
Data bit B6 has the following values:
–
0 = pressure P2 is
³
the parameter value Lower pressure critical limit P2
–
1 = pressure P2 is
<
than the lower pressure critical limit P2 parameter value
Consumption measurement input data
Data bit B7 indicates the measurement impulse of the continuous consumption measurement and has
the following values:
–
0 = Idle signal between consumption measurement impulses
–
1 = 100 ms continuous consumption measurement impulse after 200 l with consumption unit l³
–
1 = 100 ms continuous consumption measurement impulse after 10 scf with consumption unit scf
Data bit B12 has the following values:
–
0 = measurement of consumption V0 not active
–
1 = measurement of consumption V0 active