72
Festo — MSE6-C2M — 2022-08b
Parameterisation
Module parameter: monitor limit value startup
Function number
4828 + m * 64 + 7
m = module number 0
Description
Specifies the time after the supply voltage has been switched on, during which
the limit value monitoring is deactivated.
Bit
Bit 0 … 7: limit value monitoring startup
Values
Meaning
0
0 s
1
3 s
2
5 s
3
10 s, default
4
30 s
5
60 s
6
120 s
7
300 s
8 … 255
Not permissible
Comment
If parameter monitoring is active, Pm.0.7, invalid values will result in parameter-
isation error FN29
Tab. 51: Monitor limit value module parameter startup