Functions
5.2.2.1
Output word Am.0 module control
The output word Am.0 controls the pressure control function and blocking function as well as the
consumption measurement.
Data format of output word 16 bits, right-justified
D15
D14
D13 D12 D11 D10 D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
B15
B14
B13 B12 –
–
–
–
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Abbreviations used
B0
Shut-off valve controller
B1
Auto-user controller
B2
Q_low-Timer-Reset
B3, B4
Selection of user target pressure
B5
Auto enable controller
B6
Electrical controller output 0
B7
Electrical controller output 1
B12
Consumption V0 Run
B13
Consumption V0 Reset
B14
Consumption V1 Run
B15
Consumption V1 Reset
––
Reserved data bits
D0 … D15
16 bit output data field
MSB/LSB
Most significant bit/least significant bit
Tab. 8: Data format of output word Am.0
Output data, pressure regulation and blocking function
Data bit B0 has the following values:
–
0 = shut-off valve open, pressurisation state, default
–
1 = shut-off valve closed, blocking state
Data bit B1 has the following values:
–
0 = user-controlled pressure regulation and blocking function active operating mode, default
–
1 = automatic pressure control regulation and blocking function active operating mode
Data bit B2 has the following values:
–
0 = no status change of the Q_low-Timers, default
–
1 = Resetting the Q_low-Timers
Data bits B3 and B4 have the following values:
–
0 = user-controlled setpoint pressure = power-on setpoint pressure, depending on Pm.28.2, default
–
1 = user-controlled target pressure = 2.5 bar