Installation
NOTICE
Damage to internal electronics.
Damage to components and malfunctions due to incorrect handling.
• Observe the handling specifications for electrostatically sensitive devices.
The following applies for the MSE6-C2M-...-M with CPX-Extension series 1 connection:
NOTICE
Material damage as a result of changing the connecting cable when the supply voltage is switched
on
• Connect and remove the CPX-Extension connecting cable only when the supply voltage is switched
off for the control extension series 1 device.
• Only use pre-assembled connecting cables.
Electrical protection
The maximum permissible current load of the system supply for the MSE6-C2M-...-M with CPX-Exten-
sion is 6 A.
–
Use a fuse with maximum 6 A for the operating voltage 24 V DC U
EL/SEN
.
–
Use a fuse with maximum 6 A for the load voltage supply 24 V DC U
OUT
.
Installation
1. Connect the earth terminal.
2. Connect the CPX-Extension connecting cable, only for MSE6-C2M-...-M
3. Connect the fieldbus cable.
4. Connect the power supply and electrical inputs and outputs.