Diagnostic messages
98
Festo – GDCP-CMMP-M3-FW-EN – 1203NH
Diagnostic messages of the CMMP-AS-...-M3
No.
Reaction
Actions
Causes
Message
Code
13-0
–
CAN bus timeout
Error message from man-
ufacturer-specific pro-
tocol.
•
Check the CAN para-
metrisation
Config-
urable
14-0
–
Insufficient
power supply for
identification
Current regulator para-
meters cannot be determ-
ined (because of insuffi-
cient supply).
The available intermedi-
ate circuit voltage is too
low to carry out the meas-
urement.
PS off
14-1
–
Identification of
current regulator:
measurement
cycle insufficient
Too few or too many
measurement cycles re-
quired for the connected
motor.
Automatic determination
of parameters has sup-
plied a time constant out-
side the parameterisable
value range.
•
The parameters must
be manually optim-
ised.
PS off
14-2
–
Automatic para-
meter identifica-
tion: Timeout
during waiting
The output stage has not
been enabled.
•
Check the connection
of DIN4.
PS off
14-3
–
Automatic para-
meter identifica-
tion: Cancel
Power stage enable was
switched off while identi-
fication was in progress.
•
Check the sequence
control.
PS off
14-5
–
Automatic angle
encoder paramet-
er identification:
Missing index
pulse
The index pulse could not
be found following execu-
tion of the maximum per-
missible number of elec-
trical revolutions.
•
Check the index pulse
signal.
•
Angle encoder para-
metrised correctly?
PS off
14-6
–
Automatic angle
encoder paramet-
er identification:
Faulty Hall signals
Hall signals faulty or in-
valid.
The pulse train or seg-
menting of the Hall sig-
nals is inappropriate.
•
Check connection.
Refer to the technical
data to check whether
the encoder shows
three Hall signals with
120
°
or 60
°
segments;
if necessary, contact
Technical Support.
PS off