Diagnostic messages of the CMMP-AS-...-M3
No.
Reaction
Actions
Causes
Message
Code
11-3
8A83
h
Homing: timeout
The parametrised maxim-
um time for the homing
run was exceeded before
the homing run was com-
pleted.
•
Check the time setting
in the parameters.
Config-
urable
11-4
8A84
h
Homing: wrong /
invalid limit
switch
–
Relevant limit switch
not connected.
–
Limit switches
swapped?
–
No reference switch
found between the
two limit switches.
–
Reference switch is at
the limit switch.
–
Method “current posi-
tion with zero im-
pulse”: limit switch
active in the area of
the zero pulse (not
permissible).
–
Both limit switches
active at the same
time.
•
Check whether the
limit switches are con-
nected in the correct
direction of travel or
whether the limit
switches have an ef-
fect on the intended
inputs.
•
Reference switch con-
nected?
•
Check configuration of
the reference
switches.
•
Move limit switch so
that it is not in the
zero pulse area.
•
Check limit switch
parametrisation (N/C
contact/N/O contact).
Config-
urable
11-5
8A85
h
Homing: I
@
t / fol-
lowing error
–
Acceleration ramps
not suitably paramet-
rised.
–
Reversing due to pre-
mature triggering of
following error; check
parametrisation of fol-
lowing error.
–
No reference switch
reached between the
end stops.
–
Zero pulse method:
end stop reached
(here not permiss-
ible).
•
Parameterise the ac-
celeration ramps so
they are flatter.
•
Check connection of a
reference switch.
•
Method appropriate
for the application?
Config-
urable