Diagnostic messages
120
Festo – GDCP-CMMP-M3-FW-EN – 1203NH
Diagnostic messages of the CMMP-AS-...-M3
No.
Reaction
Actions
Causes
Message
Code
68-1
–
EtherNet/IP:
General commu-
nication error
A serious error was detec-
ted in the EtherNet/IP in-
terface.
•
Try to acknowledge
the error.
•
Carry out a reset.
•
Replace the interface.
•
If the error continues,
contact Technical Sup-
port.
Config-
urable
68-2
–
EtherNet/IP:
Connection has
been closed
The connection was
closed via the controller.
A new connection to the
controller must be con-
structed.
Config-
urable
68-3
–
EtherNet/IP:
Connection inter-
ruption
A connection interruption
occurred during opera-
tion.
•
Check the cabling
between
CMMP-AS-...-M3 and
controller.
•
Construct a new con-
nection to the control-
ler.
Config-
urable
68-6
–
EtherNet/IP:
Duplicate net-
work address on
hand
At least one device with
the same IP address ex-
ists in the network.
Use unique IP addresses
for all equipment in the
network.
Config-
urable
69-0
–
EtherNet/IP:
Minor error
A minor error was detec-
ted in the EtherNet/IP in-
terface.
•
Try to acknowledge
the error.
•
Carry out a reset.
Config-
urable
69-1
–
EtherNet/IP:
Incorrect IP con-
figuration
An incorrect IP configura-
tion has been detected.
Correct the IP configura-
tion.
Config-
urable
69-2
–
EtherNet/IP:
Fieldbus interface
not found
There is no EtherNet/IP
interface in the slot.
Check whether an Ether-
Net/IP interface is in the
Ext2 slot.
Config-
urable
69-3
–
EtherNet/IP:
Interface version
not supported
There is an EtherNet/IP
interface with incompat-
ible version in the slot.
Carry out a firmware up-
date on the most current
motor controller firm-
ware.
Config-
urable