6
Functions
Festo – GDCP-CMMP-M3-FW-EN – 1203NH
23
The following settings are possible:
Command
Function
Sync
Synchronisation is activated when positioning is started, if it was not already. If
the master is not stationary when positioning starts, the offset that occurs will
be made up in a controlled manner. The positioning speed used for this corres-
ponds to the speed of the master plus the positioning speed entered in the posi-
tioning record as an excessive increase in speed. The entries of the started posi-
tioning record are likewise used for the accelerations.
Sync Out
Synchronisation is deactivated when positioning is started, if it was not already.
Positioning starts with the current synchronous positioning speed (rotational
speed of the master). This results in controlled desynchronisation.
No Sync
Synchronisation is deactivated when positioning is started, if it was not already.
Positioning starts with the values for speed and acceleration entered in the posi-
tioning record.
Tab. 6.2
Commands for synchronisation
Remaining Distance
Enter the amount for the remaining distance message.
TFF (torque feed forward)
This value is used to permit the motor greater dynamic response during acceleration when large loads
are moved. The current required for approaching is increased by the set percentage (related to the
nominal current of the motor) after the positioning record is started. The result is a higher starting
torque that facilitates greater dynamic response. The value is determined experimentally.
Torque limitation
During standard positioning, the torque is limited only by the set nominal or peak currents. Torque limit-
ation provides another way of further limiting the torque during active positioning. The value should be
less than the set nominal current.
Start Delay
Waiting time until positioning starts.
Summary of Contents for CMMP-AS-***-M3 Series
Page 131: ......