Diagnostic messages
Festo – GDCP-CMMP-M3-FW-EN – 1203NH
113
Diagnostic messages of the CMMP-AS-...-M3
No.
Reaction
Actions
Causes
Message
Code
40-1
8612
h
Positive software
limit switch
The position setpoint has
reached or exceeded the
positive software limit
switch.
•
Check target data.
•
Check positioning
area.
Config-
urable
40-2
8612
h
Target position
behind the negat-
ive software limit
switch
Start of a positioning task
was suppressed because
the target lies behind the
negative software limit
switch.
•
Check target data.
•
Check positioning
area.
Config-
urable
40-3
8612
h
Target position
behind the posit-
ive software limit
switch
The start of a positioning
task was suppressed be-
cause the target lies be-
hind the positive software
limit switch.
•
Check target data.
•
Check positioning
area.
Config-
urable
41-0
–
Position set for-
warding: syn-
chronization error
Start of synchronisation
without prior sampling
pulse
•
Check the derivative
action settings in the
parameters.
Config-
urable
42-3
–
Start positioning
rejected: wrong
mode of opera-
tion
Switching of the operat-
ing mode by means of the
position set was not pos-
sible.
•
Check parametrisa-
tion of the position re-
cords in question.
Config-
urable
42-4
–
Start positioning
rejected: homing
required
A normal positioning re-
cord was started, but the
drive needs a valid refer-
ence position before
starting.
•
Execute new homing.
Config-
urable
42-5
–
Modulo position-
ing:
direction of rota-
tion is not al-
lowed
–
The positioning target
cannot be reached
through the position-
ing or edge condition
options.
–
The calculated direc-
tion of rotation is not
permitted for the
modulo positioning in
the set mode.
•
Check the chosen
mode.
Config-
urable