5
Commissioning
98
Festo – GDCP-CMMO-ST-EA-SY-EN – 2017-05c – English
Signal
Description
DOUT1…7
RECORD 1…7 (REACHED)
=1
The output will be enabled whenever the target position of the respective position
record is reached (Motion complete). The output remains active whenever the input is
reset. The output is inactive whenever a different input is enabled.
DOUT8
IN ZONE
=1
The actuator is located within the parameterised position comparator of the active
order to DIN1…7. Whenever the corresponding input 1…7 is disabled, the output
remains enabled. If, however, the actuator is pushed out of position and then returns,
the output remains disabled.
If another input RECORD 1....7 is enabled, then the current position is compared to its
position zone and output 8 is reset, depending on the result.
DOUT9
REFERENCED
=1
After a successful homing run this output is set and remains set for as long as the drive
is referenced.
DOUT10
Ready
=1
The drive is ready for operation. All requirements for starting a command record are
fulfilled:
–
Load voltage / logic voltage is present
–
Input signals [X3] STO1/STO2 = 1
–
CONTROL ENABLE = 1
–
No error
DOUT11
TORQUE LIMIT REACHED
=1
The parameterised torque/force limit has been reached.
Tab. 5.7
Valve profile: function of digital outputs