Commissioning
Festo – GDCP-CMMO-ST-EA-SY-EN – 2017-05c – English
113
5.6.5
Controller enable (CONTROL ENABLE)
Input DIN 10 controls closed-loop control enable and the power output stage.
The first time ENABLE is set after the power supply is switched on, the controller conducts a commuta
tion angle search (duration: up to 2 seconds).
On devices with a holding brake, activation of the holding brake is linked via X6.5 (BR+) to closed-loop
control enable:
–
CONTROL ENABLE 0
è
1
The controller is switched on. On devices with a holding brake, the holding brake is opened auto
matically during the switch-on delay. If no error is present, READY=1. In status ENABLE=1 the actu
ator is held in position while stationary.
–
CONTROL ENABLE 1
è
0
The ongoing order is stopped (Quick Stop). On devices with a holding brake, the holding brake is
closed automatically during the switch-off delay. After that, the closed-loop controller is switched
off and READY=0 disables ready status.
In ENABLE=0 status, no orders are accepted. On motors without a holding brake, the axis can be
offset manually.
On motors with a holding brake, the holding brake can be opened by 1-signal on the
BRAKE CONTROL input. Further information about the holding brake
è
CONTROL ENABLE
DIN10
Ready
DOUT10
Holding brake released
closed
t1
t4
t2
t3
1
2
3
PAUSE/STOP
DIN7
4
Delay times:
t1: depending on the parameterised switch-on delay
t2: depending on the mechanical inertia of the holding brake
t3: depending on the parameterised switch-off delay
t4: depending on the mechanical inertia of the holding brake
1
Request controller enable
2
Controller has been enabled
3
Revoke controller enable
4
Confirmation that controller is blocked
Fig. 5.13 Binary profile: release/inhibit controller