9-1
Chapter 9 LIST OF PERIPHERAL EQUIPMENT AND OPTIONS
The table below lists the main peripheral equipment and options that are connected to the
FRENIC-Multi. Use them in accordance with your system requirements.
For details, refer to the FRENIC-Multi User's Manual (MEH457), Chapter 6 "SELECTING
PERIPHERAL EQUIPMENT."
Name of
peripheral
equipment
Function and application
MCCBs are designed to protect the power circuits between the power control
board and inverter’s main terminals (L1/R, L2/S and L3/T for three-phase input
power supply, L1/L and L2/N for single-phase input power supply) from
overload or short-circuit which in turn prevents secondary disasters caused by
the inverter malfunctioning.
RCDs/ELCBs function in the same way as MCCBs. Use the MCCBs and
RCDs/ELCBs that satisfy the recommended rated current listed below.
w/ DCR
w/o DCR
0.1
FRN0.1E1S-2
0.2
FRN0.2E1S-2
0.4
FRN0.4E1S-2
0.75
FRN0.75E1S-2
10
1.5
FRN1.5E1S-2
15
2.2
FRN2.2E1S-2
20
3.7
FRN3.7E1S-2
20
30
5.5
FRN5.5E1S-2
30
50
7.5
FRN7.5E1S-2
40
75
11
FRN11E1S-2
50
100
15
FRN15E1S-2
75
125
0.4
FRN0.4E1S-4
0.75
FRN0.75E1S-4
1.5
FRN1.5E1S-4
10
2.2
FRN2.2E1S-4
15
3.7
FRN3.7E1S-4
4.0
FRN4.0E1S-4E *
2
5.5
FRN5.5E1S-4
15
30
7.5
FRN7.5E1S-4
20
40
11
FRN11E1S-4
30
50
15
FRN15E1S-4
40
60
0.1
FRN0.1E1S-7
0.2
FRN0.2E1S-7
0.4
FRN0.4E1S-7
10
0.75
FRN0.75E1S-7
10
15
1.5
FRN1.5E1S-7
15
20
2.2
FRN2.2E1S-7
20
30
5
5
5
5
10
20
Three-
phase
200 V
Single-
phase
200 V
Three-
phase
400 V
5
5
10
Input
power
supply
Nom inal
applied m otor
(kW )
Inverter type
Rated current of
MCCB and ELCB (A)
*
2
The FRN4.0E1S-4E is for the EU.
Note:
A box (
) in the above table replaces A, C, E, J, or K depending on the
shipping destination. For three-phase 200 V class series of inverters, it
replaces A, C, J, or K.
Select the MCCB or RCD/ELCB with appropriate breaking capacity according
to the power supply capacity.
When connecting the inverter to the power supply, add a recommended
molded case circuit breaker and earth leakage circuit breaker (with
overcurrent protection) in the path of power supply. Do not use the
devices with the rated current out of the recommenced range.
Fire could occur.
Main peri
pheral
equi
pment
Molded case
circuit breaker
(MCCB)
Residual-current-
operated
protective device
(RCD)
/Earth leakage
circuit breaker
(ELCB)*
1
*
1
with
overcurrent
protection