5-11
y codes: Link Functions
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer to
page:
y01
RS-485 Communication (Standard)
1 to 255
-
(Station address)
1
-
N
Y
1
y02
(Communications error processing)
0: Immediately trip with alarm
er8
-
-
Y
Y
0
1:
3: Continue to run
y03
(T imer) 0.0 to 60.0
0.1
s
Y
Y
2.0
y04
(Baud rate)
0: 2400 bps
-
-
Y
Y
3
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
y05
(Data length)
0: 8 bits
-
-
Y
Y
0
1: 7 bits
y06
(Parity check)
0: None (2 stop bits for Modbus RT U)
-
-
Y
Y
0
1: Even parity (1 stop bit for Modbus RT U)
2: Odd parity (1 stop bit for Modbus RT U)
3: None (1 stop bit for Modbus RT U)
y07
(Stop bits)
0: 2 bits
-
-
Y
Y
0
1: 1 bit
y08
(No-response error detection time)
0: No detection
1
s
Y
Y
0
1 to 60
y09
(Response interval) 0.00 to 1.00
0.01
s
Y
Y
0.01
y10
(Protocol selection)
0: Modbus RT U protocol
-
-
Y
Y
1
1: FRENIC Loader protocol (SX protocol)
2: Fuji general-purpose inverter protocol
y11
RS-485 Communication (Option)
1 to 255
(Station address)
1
-
N
Y
1
y12
(Communications error processing)
0: Immediately trip with alarm
erp
-
-
Y
Y
0
1:
3: Continue to run
y13
(T imer) 0.0 to 60.0
0.1
s
Y
Y
2.0
y14
(Baud rate)
0: 2400 bps
-
-
Y
Y
3
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
y15
(Data length)
0: 8 bits
-
-
Y
Y
0
1: 7 bits
y16
(Parity check)
0: None (2 stop bits for Modbus RT U)
-
-
Y
Y
0
1: Even parity (1 stop bit for Modbus RT U)
2: Odd parity (1 stop bit for Modbus RT U)
3: None (1 stop bit for Modbus RT U)
y17
(Stop bits)
0: 2 bits
-
-
Y
Y
0
1: 1 bit
y18
(No-response error detection time)
0: No detection
1
s
Y
Y
0
1 to 60
y19
(Response interval) 0.00 to 1.00
0.01
s
Y
Y
0.01
y20
(Protocol selection)
0: Modbus RT U protocol
-
-
Y
Y
0
2: Fuji general-purpose inverter protocol
y98
Frequency command
Run command
-
-
Y
Y
0
5-60
0: Follow H30 data
Follow H30 data
1: Via field bus option
Follow H30 data
2: Follow H30 data
Via field bus option
3: Via field bus option
Via field bus option
y99
Frequency command
Run command
-
-
Y
N
0
-
0: Follow H30 and y98 data
Follow H30 and y98 data
1: Via RS-485 link (Loader)
Follow H30 and y98 data
2: Follow H30 and y98 data
Via RS-485 link (Loader)
3: Via RS-485 link (Loader)
Via RS-485 link (Loader)
Retry during the period specified by timer y13.If the retry fails, trip with
alarm
erp
. If it succeeds, continue to run.
Retry during the period specified by timer y13. If the retry fails, trip with
alarm
erp
. If it succeeds, continue to run.
2:
T rip with alarm
erp
after running for the period specified by timer y13
2:
Bus Link Function (Mode selection)
Loader Link Function (Mode selection)
Name
T rip with alarm
er8
after running for the period specified by timer y03
Data setting range
Table A Default Settings Depending on the Shipping Destination
Shipping Destination
Function
code
Asia
China
EU
Japan
Taiwan and
Korea
Remarks
F03/A01
60.0 50.0 50.0 60.0 60.0
F04/A02
60.0 50.0 50.0 50.0 50.0
220
200
230
200
200
For 200 V class series
F05/A03
F06/A04
380
380
400
400
400
For 400 V class series
F14
1 1 0 1 1
F26 2 2 15 2
2
E31 60.0 50.0 50.0 60.0 60.0
E46
1 0 1 0 1