5-4
(E code continued)
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer to
page:
E29
Frequency Arrival Delay T ime
0.01 to 10.00
0.01
s
Y
Y
0.10
5-47
E30
0.0 to 10.0
0.1
Hz
Y
Y
2.5
E31
0.0 to 400.0
0.1
Hz
Y
Y
T able A *4
-
E32
(Hysteresis width) 0.0 to 400.0
0.1
Hz
Y
Y
1.0
E34
5-47
(Level)
0.01
A
Y
Y1
Y2
E35
(T imer) 0.01 to 600.00 *1
0.01
s
Y
Y
10.00
E37
0.01
A
Y
Y1
Y2
E38
(T imer) 0.01 to 600.00 *1
0.01
s
Y
Y
10.00
E39
0.000 to 9.999
0.001
-
Y
Y
0.000
5-48
E40
PID Display Coefficient A
-999 to 0.00 to 9990 *1
0.01
-
Y
Y
100
-
E41
PID Display Coefficient B
-999 to 0.00 to 9990 *1
0.01
-
Y
Y
0.00
E42
LED Display Filter
0.0 to 5.0
0.1
s
Y
Y
0.5
E43
0: Speed monitor (select by E48)
-
-
Y
Y
0
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID command
12: PID feedback amount
13: T imer
14: PID output
15: Load factor
16: Motor output
21: Reserved *2
22: Reserved *2
E45
0:
-
-
Y
Y
0
1:
E46
(Language selection)
0: Japanese
-
-
Y
Y
T able A *4
1: English
2: German
3: French
4: Spanish
5: Italian
E47
(Contrast control) 0 (Low) to 10 (High)
1
-
Y
Y
5
E48
LED Monitor (Speed monitor item)
0: Output frequency (Before slip compensation)
-
-
Y
Y
0
1: Output frequency (After slip compensation)
2: Reference frequency
3: Motor speed in r/min
4: Load shaft speed in r/min
5: Line speed in m/min
6: Constant feeding rate time
E50
0.01 to 200.00 *1
0.01
-
Y
Y
30.00
E51
0.001
-
Y
Y
0.010
E52
Keypad (Menu display mode)
0: Function code data editing mode (Menus #0 and #1)
-
-
Y
Y
0
-
1: Function code data check mode (Menu #2)
2: Full-menu mode (Menus #0 through #6)
E59
0: Current input (C1 function), 4 to 20 mADC
-
-
N
Y
0
5-48
1: Voltage input (V2 function), 0 to +10 VDC
E61
-
-
N
Y
0
5-49
E62
0: None
-
-
N
Y
0
(C1 function)
1: Auxiliary frequency command 1
E63
2: Auxiliary frequency command 2
-
-
N
Y
0
(V2 function)
3: PID command 1
5: PID feedback amount
E65
1
%
Y
Y
999
Bar charts for output frequency, current and calculated torque
100% of the
motor rated
current
Selecting function code data assigns the corresponding function to
terminals [12] and [C1] (C1/V2 function) as listed below.
0.00 : Disable
Current value of 1 to 200% of the inverter rated current
Name
Terminal [C1] Signal Definition
(C1/V2 Function)
Coefficient for Speed Indication
Terminal [12] Extended Function
Frequency Arrival
(Hysteresis width)
Frequency Detection (FDT )
Overload Early Warning/Current
Detection
LCD Monitor *3 (Item selection)
Display Coefficient for Input Watt-hour
Data
Reference Loss Detection
(Continuous running frequency)
Current Detection 2
(Level)
Terminal [C1] Extended Function
Terminal [C1] Extended Function
(Detection level)
Coefficient for Constant Feeding Rate
Time
100% of the
motor rated
current
Running status, rotational direction and operation guide
0: Decelerate to stop
20 to 120
999: Disable
0.000 (Cancel/reset
)
0.001 to 9999
Data setting range
LED Monitor (Item selection)
0.00 : Disable
Current value of 1 to 200% of the inverter rated current
5-48
The shaded function codes ( ) are applicable to the quick setup.
*
1
When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can
display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*
2
These function codes and their data are displayed, but they are reserved for particular manufacturers. Unless otherwise
specified, do not access these function codes.
*
3
These function codes are for use with an optional multi-function keypad.
*
4
Default settings for these function codes vary depending on the shipping destination. See Table A "Default Settings
Depending on the Shipping Destination" on page 5-11.