![FE FRENIC-Multi series Instruction Manual Download Page 179](http://html1.mh-extra.com/html/fe/frenic-multi-series/frenic-multi-series_instruction-manual_3750705179.webp)
8-4
8.2 Specifications of Keypad Related
8.2.1 General specifications of keypad
Table 8.1 General Specifications
Items Specification
Remarks
Protective structure
Front side: IP40, Back (mounting) side: IP20
Site to be installed
In door
Ambient temperature
-10 to 50
°
C
Ambient humidity
5 to 95% RH, no condensation allowed
Ambient air
No corrosive gas, no inflammable gas, no dust, and no
direct sunlight allowed
Altitude
1000 m or less
(Note)
Air pressure
86 to 106 kPa
Vibration
3 mm (maximum amplitude):
9.8 m/s
2
:
2 m/s
2
:
1 m/s
2
:
Within 2 to 9 Hz
Within 9 to 20 Hz
Within 20 to 55 Hz
Within 55 to 200 Hz
Storage ambient
temperature
-25 to 70
°
C
Storage ambient
humidity
5 to 95% RH (no condensation allowed)
External dimension
Refer to Section 8.4.2 "Standard keypad"
Mass
35 grams
With a keypad rear
cover
(Note) When using an inverter in a place of an altitude within 1000 m to 3000 m, you need to lower the
output current of the inverter. For details, refer to Chapter 2, Section 2.1 “Operating Environment.”
8.2.2 Communications
specifications of keypad
Table 8.2 Hardware specifications
Items Specification
Remarks
No. of linkable unit
One-to-one connection with an inverter
For a remote site
operation.
Link cable
US ANSI TIA/EIA-568A category 5 compliant straight
type cable (10BASE-T/100BASE-TX straight type)
Extension cable for the
remote site operation
(CB-5S, CB-3S,
CB-1S and etc.)
Maximum cable
length
20 m
Connector
Standard RJ-45 connector/jack
Refer to Table 8.3
Table 8.3 Pin Assignment of RJ-45 Connector
Pin number
Signal
Description
Remarks
1 and 8
Vcc
Power supply lines for keypad
5 VDC
2 and 7
GND
Reference potential
0 V
3 and 6
NC
Reserved
4
DX-
RS-485 communications data line (-)
5
DX+
RS-485 communications data line (+)
Summary of Contents for FRENIC-Multi series