8-2
8.1.2 Three-phase 400 V class series
*1
Fuji 4-pole standard motor
*2
Rated capacity is calculated assuming the output rated voltage as 440 V.
*3
Output voltage cannot exceed the power supply voltage.
*4
Use the inverter at the current enclosed with parentheses ( ) or below when the carrier frequency is set to 4 kHz
or above (F26) and the inverter continuously runs at 100% load.
*5
The value is calculated assuming that the inverter is connected with a power supply with the capacity of 500 kVA
(or 10 times the inverter capacity if the inverter capacity exceeds 50 kVA) and %X is 5%.
*6
Obtained when a DC reactor (DCR) is used.
*7
Average braking torque obtained when reducing the speed from 60 Hz with AVR control OFF. (It varies with the
efficiency of the motor.)
*8
Average braking torque obtained by use of an external braking resistor (standard type available as option)
*9
The nominal applied motor rating of FRN4.0E1S-4E to be shipped to the EU is 4.0 kW.
*10
3)
61800
(IEC
67
×
(V)
voltage
average
phase
-
Three
(V)
voltage
Min
-
(V)
voltage
Max
(%)
unbalance
Voltage
=
-
If this value is 2 to 3%, use an optional AC reactor (ACR).
Note:
A box (
) in the above table replaces A, C, E, J, or K depending on the shipping destination.