5-8
(H code continued)
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer to
page:
H68
Slip Compensation 1
0:
-
-
N
Y
0
5-32
(Operating conditions)
1:
2:
3:
H69
Automatic Deceleration
0: Disable
-
-
Y
Y
0
5-62
(Mode selection)
2:
4:
H70
Overload Prevention Control
0.01
Hz/s
Y
Y
999
5-63
H71
Deceleration Characteristics
0: Disable
-
-
Y
Y
0
1: Enable
H76
0.0 to 400.0
0.1
Hz
Y
Y
5.0
5-62
H80
0.00 to 0.40
0.01
-
Y
Y
0.20
-
H89
Reserved *2
0, 1
-
-
Y
Y
0
H90
Reserved *2
0, 1
-
-
Y
Y
0
H91
Reserved *2
0, 1
-
-
Y
Y
0
H94
Cumulative Motor Run T ime 1
Change or reset the cumulative data
-
-
N
N
-
5-63
H95
0: Slow
-
-
Y
Y
1
5-28
1: Quick
H96
Data
ST OP key priority Start check function
-
-
Y
Y
0
-
0:
Disable
Disable
1:
Enable
Disable
2:
Disable
Enable
3:
Enable
Enable
H97
Clear Alarm Data
-
-
Y
N
0
5-62
H98
-
-
Y
Y
5-63
(Mode selection) Bit 0 : Lower the carrier frequency automatically
Bit 1 : Detect input phase loss
Bit 2 : Detect output phase loss
Bit 4 : Judge the life of DC link bus capacitor
Disable during ACC/DEC and disable at base frequency or above
Enable (Canceled if actual deceleration time exceeds three times the
one specified by F08/E11.)
Disable during ACC/DEC and enable at base frequency or above
Enable during ACC/DEC and disable at base frequency or above
19
(bit4,
1,0
=
1)
0 to 31: Display data on the keypad's LED monitor in decimal format
(In each bit, "0" for disabled, "1" for enabled.)
Bit 3 : Select life judgment threshold of DC link bus capacitor
Data setting range
T orque Limiter (Frequency increment
limit for braking)
Name
0.00 : Follow deceleration time specified by F08/E11
0.01 to 100.0
999: Disable
Setting H97 data to "1" clears alarm data and then returns to zero.
Enable (Not canceled if actual deceleration time exceeds three times
the one specified by F08/E11.)
Enable during ACC/DEC and enable at base frequency or above
Output Current Fluctuation Damping
Gain for Motor 1
ST OP Key Priority/Start Check Function
Protection/Maintenance Function
DC Braking
(Braking response mode)
A codes: Motor 2 Parameters
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer to
page:
A01
Maximum Frequency 2
25.0 to 400.0
0.1
Hz
N
Y
T able A *4
-
A02
Base Frequency 2
25.0 to 400.0
0.1
Hz
N
Y
T able A *4
A03
0:
1
V
N
Y2
T able A *4
80 to 240:
160 to 500:
A04
Maximum Output Voltage 2
80 to 240V:
1
V
N
Y2
T able A *4
160 to 500V:
A05
Torque Boost 2
0.1
%
Y
Y
Depending
on the
inverter
capacity
A06
1: For a general-purpose motor with shaft-driven cooling fan
-
-
Y
Y
1
2:
A07
(Overload detection level)
0.01
A
Y
Y1
Y2
100% of the
motor rated
current
A08
(T hermal time constant) 0.5 to 75.0
0.1
min
Y
Y
5.0
A09
DC Braking 2
0.0 to 60.0Hz
(Braking starting frequency)
0.1
Hz
Y
Y
0.0
A10
(Braking level) 0 to 100
1
%
Y
Y
0
A11
(Braking time)
0.01
s
Y
Y
0.00
A12
Starting Frequency 2
0.1 to 60.0
0.1
Hz
Y
Y
0.5
A13
0: Variable torque load
-
-
N
Y
1
1: Constant torque load
2: Auto-torque boost
3:
4:
5:
0.0 to 20.0
(percentage with respect to "A03: Rated Voltage at Base Frequency 2")
Note: This setting takes effect when A13 = 0, 1, 3, or 4.
Name
Output a voltage in proportion to input voltage
Output an AVR-controlled voltage (for 200 V class series)
Auto-energy saving operation (Constant torque load during ACC/DEC)
Auto-energy saving operation (Auto-torque boost during ACC/DEC)
Output an AVR-controlled voltage (for 200 V class series)
Output an AVR-controlled voltage (for 400 V class series)
For an inverter-driven motor, non-ventilated motor, or motor with
separately powered cooling fan
Auto-energy saving operation (Variable torque load during ACC/DEC)
0.00 : Disable
0.01 to 30.00
0.00: Disable
1 to 135% of the rated current (allowable continuous drive current) of the
motor
Data setting range
Electronic T hermal Overload Protection
for Motor 2
(Select motor characteristics)
Rated Voltage at Base Frequency 2
Output an AVR-controlled voltage (for 400 V class series)
Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 2
*
2
These function codes and their data are displayed, but they are reserved for particular manufacturers. Unless otherwise
specified, do not access these function codes.
*
4
Default settings for these function codes vary depending on the shipping destination. See Table A "Default Settings
Depending on the Shipping Destination" on page 5-11.