The configured signal will make pulses of the adjusted milliseconds
while the input signal is activated.
By default, outputs configuration is:
OUTPUT
LOGICAL
GATE
BINARY STATES
LEDs
LED 1
OR4_PULSES
•
Ready
LED 2
OR4_LATCH
•
50P1 Trip
•
50P2 Trip
•
51P Trip
LED 3
OR4_LACTH
•
50N1 Trip
•
50N2 Trip
LED 4
OR4_LACTH
•
50BF Trip
LED 5
OR4_LACTH
•
67N-1 Trip
•
67N-2 Trip
•
67NI-1 Trip
•
67NI-2 Trip
LED 6
OR4_LACTH
•
74TCS Alarm
LED 52
OR4
•
52 Closed
LED 79
OR4
•
79 Standby
PHYSICAL
OUTPUTS
Output 1
OR4
•
Ready
Output 2
OR4
•
79 Close time
•