Rev.06
87/226
6.
TECHNICAL SPECIFICATIONS AND STANDARDS
6.1.
Technical Specifications
SIL-D
50(2)
Function permission: Yes/No
Operating range: 0.10 to 30 xIn (step 0.01)
Time delay: 0.02 to 300 s (step 0.01 s)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Timing accuracy: ±30 ms or ±0.5% (greater of both)
50N/G(2)
Function permission: Yes/No
Operating range: 0.10 to 30 xIn (step 0.01)
Time delay: 0.02 to 300 s (step 0.01 s)
Activation level 100%
Deactivation level 95%
Instantaneous deactivation
Timing accuracy: ±30 ms or ±0.5% (greater of both)
50/51
Function permission: Yes/No
Operating range: 0.10 to 7 xIn (step 0.01)
Curves IEC 60255-151 and ANSI
Time delay: IEC Inverse curve, IEC very inverse curve,IEC extremely inverse curve IEC long time inverse,
IEEEInverse curve, IEEEvery inverse curve, IEEEextremely inverse curve.
Defined time : 0.02 to 300 s (step 0.01 s)
Dial: 0.02 to 2.20 (step 0.01)
Curve, activation level 110%
Curve, deactivation level 100%
Defined time, activation level 100%
Defined time, deactivation level 95%
Instantaneous deactivation
Timer accuracy: ±5% or ±30 ms (whichever is greater)
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...