Rev.06
28/226
Application example:
Starting from the following information:
Directional characteristic data:
•
Directionality: Forward
•
Operation angle: 90º
•
Halfcone angle: 85º
Installation’s residual values data:
•
Residual current: 1A
•
Polarization voltage: 40V
•
Operating time: Definite time of 0.1 seg.
67N parameters:
•
Permission: Yes
•
Curve: Definite time
•
Tap: 1 (In=1)
•
Operating time: 0.1
•
Directionality: Forward
•
Voltage: 40V
•
Operating angle: 90º
•
Halfcone angle: 90º
The operation area will be defined according the following characteristic:
With these settings, when a residual current is higher than 1A, delayed more than 15º and less
than 165º on the residual voltge, if the residual voltage is higher than 40V, the function 67N will
act in a time of 0.1 sec.