Rev.06
186/226
X
203
<11>
67NI Disparo
2
SE
X
203
<12>
67NI2 Start
2
SE
X
203
<13>
67NI2 Trip
2
SE
(**) Type Identification 9 : Measurands II (Measurements IL123, VL123, P, Q, f)
SIL-D relay uses this type to send the value of the currents IL1, IL2 and IL3, the other
measures remain with value 0.
Each current value is in the range 0
– 4095 where 4095 corresponds to 1,2*In
e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A
Selection of standard information numbers in control direction
SIL-D
FUN
INF
Description
TYP
COT
System functions in control direction
X
160
<0>
Initiation of general interrogation
7
Init of GI
X
160
<0>
Time synchronization
6
TS
General commands in control direction
X
160
<16>
Auto-recloser on (1) / off (0)
20
ACK,NACK
X
160
<19>
LED reset (0)
20
ACK,NACK
Particular commands in control direction
X
200
<1>
CB close (1) / open (0)
20
ACK,NACK
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...