Rev.06
38/226
4.8. Function 50BF. Circuit Breaker opening failure
This function settings are as follows:
Group
Description
Minimum
Maximum
Step
Unit
Default
50BF
Circuit breaker opening fault
Permission
-
-
Yes/No
-
No
Opening fault time
0.02
1.00
0.01
s
0.2
The following automaton describes the open fault function:
When the “50BF init” status is activated, a switch is made to the "50BF init" and time is counted.
If, following the adjusted open fault time, the switch is not detected to have open, the function
trips. The function is reset when the circuit breaker
is detected to have opened, and the “50BF
init
” status has been reset.
To monitor the circuit breaker opening the current measurement via the three phases is used.
When the current via the three phases is less than 8% of the rated current, the circuit breaker is
considered to be open.
There is a signal
“50BF init” to start the open fault from an external protection. The “50BF init” is
configurable by user. The default configuration is shown below:
•
General trip
Run
Pickup
INIT_50BF = 1
Reset
t >
Imax< 8% Inominal
Imax< 8% Inominal
Imax< 8% Inominal
INIT_50BF = 0
50BF
Trip
50BF
50BF
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...