Rev.06
212/226
12.14. Examples od Modbus frames
Reading of the protection status
Id.
Trans
Id.
Protocol
Length
Address
Function
Init Addr.
MSB
Init Addr.
LSB
Num. Reg.
MSB
Num. Reg.
LSB
08 F4
00 00
00 04
03
01
01
90
00
01
And the SIL-D will reply:
Id. Trans
Id. Protocol
Length
Address
Function
Number
of bytes
Status
08 F4
00 00
00 04
03
01
01
01
Reading the measurement from the phase A current of equipment 3
Id.
Trans
Id.
Protocol
Lenght
Address
Function
Init Addr.
MSB
Init Addr.
LSB
Num. Reg.
MSB
Num. Reg.
LSB
66 96
00 00
00 06
03
03
01
2C
00
02
And SIL-D will reply with the IA measurement in UINT16 format:
Id. Trans
Id. Protocol
Length
Address
Function
Number
of bytes
Register 0
Register 1
66 96
00 00
00 07
03
03
04
0A 7B
00 00
It is an integer value of 2683, being la In=1A, 4095 is 1,2*1A, then 2683 will be 0,786A
Close Circuit breaker command
Id.
Trans
Id.
Protocol
Lenght
Address
Function
Init Addr.
MSB
Init Addr.
LSB
Data
1F 6A
00 00
00 06
03
05
00
C8
FF 00
And SIL-D will reply:
Id. Trans
Id. Protocol
Lenght
Address
Function
Init Addr.
MSB
Init Addr.
LSB
Data
1F 6A
00 00
00 06
03
05
00
C8
FF 00
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...