7.5.
Setting up the session: Password and access levels
Users must identify themselves with a password in order to Pickup communications and to
change the equipment settings or configuration using the HMI. Depending on the access
level, it may or may not be possible to perform the operations shown on the table below.
ACCESS
LEVEL
Read-only permission:
Status and measurements
Settings
Events
Permission to:
Change settings
Download and Delete the
Events buffer
Permission to:
Execute
Commands
Permission to:
Change
Configuration
Permission to
Change
Protected
Settings
1
YES
YES
NO
NO
YES
2
YES
YES
NO
NO
NO
3
YES
NO
YES
NO
NO
4
YES
YES
YES
NO
NO
5
YES
YES
YES
YES
NO
Four passwords and their associated levels of access are set up when the equipment is
configured using the SIcom program. Four passwords and their associated levels of
access are set up when the equipment is configured using the SIcom program. It is
possible to change the passwords The password must have 4 characters. By default, the
equipment is programmed with the following passwords and their associated levels:
PASSWORD
ACCESS LEVEL
2222
2
3333
3
4444
4
5555
5
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...