Rev.06
82/226
We are going to use configuration by default as an example:
OUTPUT
LOGICAL
GATE
BINARY
STATES
DESCRIPTIONS
LED 1
OR4_PULSES
•
Ready
Led On blinks when internal signal “READY” of
general state of the device is activated, this
indicates that the device is working correctly
without any failures.
LED 2
NOR4
•
Ready
Led alarm will activate when internal signal
“READY” of general state of the device is
deactivated, this indicates some failure has
occurred.
LED 3
OR4_LACTH
•
General Trip
Led trip will activate when internal signal
“GENERAL TRIP” of general state of the device is
activated, this indicates that some protection
function has tripped. This led will continue
activated until the reset of the leds is made.
Output 1
OR4
•
Local opening
•
General trip
Trip output will activate when there is a general
trip or when 52 opening command is carried out,
from local communications or from HMI.
Output 2
OR4
•
Local closing
Output 2 will be activated when 52 closing
command is carried out from local communications
or from HMI.
52b
OR4
•
Input-2
When physical input 2 is activated, 52a logical
output will be activated, and it will used to
determine the breaker state.
External trip
OR4
•
Input-1
When physical input 1 is activated external trip
logical output will be activated, and it will be used
to generate a general trip by general protection
function.
50BF Init
OR4
•
Local opening
•
Remote opening
•
General trip
When a general trip has occurred or when 52a
opening command is carried out from local
communications start 50BF logical output will be
activated and it will be used to initiate the
detection of breaker failure by 50BF function.
Fault Init
OR4_LACTH
•
General trip
When general trip is activated, fault start logical
output will be activated and it will generate a new
fault register.
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...