Rev.06
90/226
CLP
Function permission: Yes/No
Settings group: 1 to 4 (step 1)
No load Time: 0.02 to 300 s (step 0.01 s)
Cold load Time: 0.02 to 300 s (step 0.01 s)
CLP activation threshold: 8% In
CLP reset threshold: 10% In
PLC
OR4, OR4_LATCH, OR4_PULSES, OR4_TIMERUP, OR4_PULSE, NOR4, NOR4_LATCH,
NOR4_TIMERUP, NOR4_PULSE, AND4, AND4_PULSES, AND4_TIMERUP, AND4_PULSE, NAND4,
NAND4_TIMERUP, NAND4_PULSE, NOR4_PULSES
86
Allows to latch (lock out) the contact trip due to programmable logic (PLC: LATCH).
49T
Available through configurable inputs thanks to the programmable logic
Trip Block
Blocking: Yes/No
Blocking limit: 1.5 to 20 x In (step 0.01)
Settings tables
4 settings tables
Activated by inputs or by general settings.
RTC
Capacitor charge time: 10 minutes
Operation with no auxiliary voltage: 72 hours
Oscillography
16 samples/cycle
Fault init configurable
5 records of 100 cycles: 3 prefault and 97 postfault cycles
COMTRADE IEEE C37.111-1991
4 analog channels y 48 digital channels
Fault reports
20 fault reports with 24 events each one
Demand of current
Demand of current with the following characteristics:
•
Number of records: 168
•
Recording mode circular
•
Sampling rate (interval): configurable through communications: 1
– 60 min
•
Record format:
Date/Time
IMAX (in interval)
IMAX (actual)
IA
IB
IC
IN
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...