Profiles for PHOENIX MIG/MAG systems
Profiles for the Interbus-S (copper),
Interbus-S LWL (FSMA) and Interbus-S (Rugged Line) modules
Item No.: 099-008225-EWM01
39
7
Profiles for PHOENIX MIG/MAG systems
The BUSINTX11 has a selection option for what are known as signal profiles which can be selected via a
selector switch with 16 settings.
The number of profiles available depends on the field bus standard being used and on the module
software version. The profiles described below therefore represent a minimum of the available
functionality in each case and are being updated on a continuous basis.
A newly selected profile is only applied once the module has been isolated from any supply voltage and
supplied with power again.
In cases where a switch position to which no profile is assigned is selected, the default profile is activated
for the module and an error message is displayed on the module (but not on the field bus). The module is
still ready for operation, however.
Depending on the profile, it may be that different signals in the description are not present or are not
used.
7.1
Profiles for the Interbus-S (copper),
Interbus-S LWL (FSMA) and Interbus-S (Rugged Line) modules
7.1.1
Default profile (switch position 0)
The module uses a data capacity of 6 words (12 bytes) for input data and output data.
Actuation data
Byte
no.
Bit no.
Function
Description
0
0&1
Select operating mode
Bit allocation:
Bit1 Bit0
0 0
0 1
1 0
1 1
Select between non-latched/special non-latched
Non-latched operating mode
Not used
Not used
Special non-latched operating mode
0
2
Select welding mode
Bit allocation:
0
1
Select between normal/pulse welding
Normal welding active
Pulse welding active
0
3
Check monitoring function
Bit allocation:
0
1
Activate/deactivate welding parameter monitoring
Monitoring deactivated
Monitoring activated
0 4 Start
Bit allocation:
0
1
Start signal to initiate the welding process
Signal stop on system
Signal start on system
0 5 Robot
ready
Bit allocation:
0
1
Safety signal for rapid shut-down
No ready message from robot, no start possible,
rapid shut-down carried out in the process
Robot ready message, start is possible
0
6
Gas test 1
Bit allocation:
0
1
Manual check via the blow-out valve
Blow-out valve off
Blow-out valve on