Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
90
Hauser
ZERO POSITION (814)
Entry
Enter value for level offset.
If the measurement should not start at the mounting location of the device, e.g. for
containers with a sump, carry out zero point shift (level offset).
Prerequisite:
• CALIBRATION MODE = Dry
P01-PMP75xxx-19-xx-xx-xx-001
Fig. 35:
Zero point shift
1
Device is mounted above the level lower range value: a positive value has to be
entered for ZERO POSITION.
2
Device is mounted below the level lower range value: a negative value has to be
entered for ZERO POSITION.
Factory setting:
0.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant
).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 13: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",