Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
75
UNIT VOLUME (313)
Selection
Select volume unit.
Prerequisite:
• LIN. MEASURAND = Volume
Options:
• l
• hl
• cm
3
• dm
3
• m
3
• m
3
E
3
• ft
• ft
3
E
3
• gal
• Igal
• bbl
• User unit,
see also the following parameter description for CUSTOMER UNIT V and
CUST. UNIT FACT. V.
Factory setting:
m
3
CUSTOMER UNIT V (608)
Entry
Enter text (unit) for customer-specific volume unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST. UNIT FACT. V
Prerequisite:
• LIN. MEASURAND = Volume, UNIT VOLUME = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. V (607)
Entry
Enter conversion factor for a customer-specific volume unit.
The conversion factor must be entered in relation to the SI unit "m
3
".
See also CUSTOMER UNIT V.
Prerequisite:
• LIN. MEASURAND = Volume, UNIT VOLUME = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 0.01 m3
i
1 bucket
– Entry CUSTOMER UNIT V: bucket
– Entry CUST. UNIT FACT. V: 100
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
TANK VOLUME (858)
Entry
Enter tank volume.
Prerequisite:
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Factory setting:
1.0 m
3
Table 11: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description