Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
123
MEAS. VAL. TREND (378)
Display
Displays the trend of the pressure measured value.
Possibilities: increasing, decreasing, constant
LEVEL BEFORE LIN (050)
Display
Displays the level value prior to linearisation.
Prerequisite:
• LEVEL MODE = Linear or Height Linearized
Depending on the setting for the LIN. MEASURAND or COMB. MEASURAND
parameter, this parameter displays the current level in % or in a unit of level.
TANK CONTENT (370)
Display
Displays the level value after linearisation.
Prerequisite:
• LEVEL MODE = Pressure Linearized or Height Linearized
Depending on the settings for the LINd. MEASURAND or COMB. MEASURAND
parameter, the current tank content is displayed in % or in a unit of volume or mass. This
value corresponds to the MEASURED VALUE.
Table 29: (GROUP SELECTION
) OPERATING MENU
PROCESSINFO
PROCESS VALUES "Flow"
Parameter name
Description
Prerequisite
:
• MEASURING MODE = Flow (
MEASURED VALUE (679)
Displays the measured value
In the "Flow" measuring mode, this value corresponds to the SUPPRESSED FLOW
parameter.
Prerequisite:
• Digital communication
On-site operation:
• For on-site operation, the MEASURED VALUE parameter is displayed on the 1st level.
PRESSURE (301)
Display
Displays the measured pressure after sensor recalibration, position adjustment and
damping. This value corresponds to the MEASURED VALUE parameter in the "Pressure"
measuring mode.
P01-xMx7xxxx-05-xx-xx-xx-011
CORRECTED PRESS. (434)
Display
Displays the measured pressure after sensor trim and position adjustment and before
damping.
See also PRESSURE diagram.
SENSOR PRESSURE (584)
Display
Displays the measured pressure before sensor trim, position adjustment and damping.
See also PRESSURE diagram.
SENSOR TEMP. (367)
Display
Displays the temperature currently measured in the sensor. This temperature can deviate
from the process temperature.
MEAS. VAL. TREND (378)
Display
Displays the trend of the pressure measured value.
Possibilities: increasing, decreasing, constant
SUPPRESSED FLOW (375)
Display
Displays the current flow. Depending on the flow mode selected (
FLOW-MEAS.
TYPE), a volume flow, mass flow, standard volume flow or corrected volume flow is
displayed.
Table 28: (GROUP SELECTION
) OPERATING MENU
PROCESSINFO
PROCESS VALUES "Level"
Parameter name
Description
P
I
Sensor
Current
output
Pressure
Level
Flow
PRESSURE
Damping
CORRECTED
PRESS.
Position
adjust-
ment
Sensor
trim
SENSOR
PRESSURE