Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Level measurement
Hauser
29
5
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION
OPERATING MENU
SETTINGS
BASIC SETUP
6
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
7
Select the "Pressure Linearized" option by means of the
LEVEL MODE parameter. See also the following note,
point 3.
8
Select the "Volume" option by means of the LINd.
MEASURAND parameter.
9
Select a volume unit via the UNIT VOLUME parameter,
here m
3
for example.
10
Select HYDR. PRESS MIN. parameter.
Enter the minimum hydrostatic pressure to be expected,
here 0 mbar for example.
11
Select HYDR. PRESS MAX
.
Enter the maximum hydrostatic pressure to be expected.
Carry out linearisation:
12
Change the function group:
Menu path: (GROUP SELECTION
) OPERATING
MENU
SETTINGS
LINEARISATION
13
Select TANK CONTENT MIN parameter.
Specify the minimum tank contents to be expected, here
0 m
3
for example.
14
Select TANK CONTENT MAX parameter.
Specify the maximum tank contents to be expected, here
3.5 m
3
for example.
15
On-site display:
Select the "Editor table" option by means of the TABLE
SELECTION parameter.
16
Select the "Semiautomatic" option by means of the LIN.
EDIT MODE parameter.
17
Select the "New table" option by means of the EDITOR
TABLE parameter.
Description