Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
122
Hauser
PRESSURE (301)
Display
Displays the measured pressure after sensor recalibration, position adjustment and
damping. This value corresponds to the MEASURED VALUE parameter in the "Pressure"
measuring mode.
P01-xMx7xxxx-05-xx-xx-xx-009
CORRECTED PRESS. (434)
Display
Displays the measured pressure after sensor trim and position adjustment and before
damping.
See also PRESSURE diagram.
SENSOR PRESSURE (584)
Display
Displays the measured pressure before sensor trim, position adjustment and damping.
See also PRESSURE diagram.
SENSOR TEMP. (367)
Display
Displays the temperature currently measured in the sensor. This temperature can deviate
from the process temperature.
MEAS. VAL. TREND (378)
Display
Displays the trend of the pressure measured value.
Possibilities: increasing, decreasing, constant
Table 28: (GROUP SELECTION
) OPERATING MENU
PROCESSINFO
PROCESS VALUES "Level"
Parameter name
Description
Prerequisite
:
• MEASURING MODE = Level (
see also Page 45).
MEASURED VALUE (679)
Displays the measured value
In the "Level" measuring mode with "Linear" or "Pressure Linearized" level type, this
value corresponds to the LEVEL BEFORE LIN parameter
In the "Level" measuring mode with "Height Linearized" level type, this value corresponds
to the TANK CONTENT parameter.
Prerequisite:
• Digital communication
On-site operation:
• For on-site operation, the MEASURED VALUE parameter is displayed on the 1st level.
PRESSURE (301)
Display
Displays the measured pressure after sensor recalibration, position adjustment and
damping. This value corresponds to the MEASURED VALUE parameter in the "Pressure"
measuring mode.
P01-xMx7xxxx-05-xx-xx-xx-010
CORRECTED PRESS. (434)
Display
Displays the measured pressure after sensor trim and position adjustment and before
damping.
See also PRESSURE diagram.
SENSOR PRESSURE (584)
Display
Displays the measured pressure before sensor trim, position adjustment and damping.
See also PRESSURE diagram.
SENSOR TEMP. (367)
Display
Displays the temperature currently measured in the sensor. This temperature can deviate
from the process temperature.
Table 27: (GROUP SELECTION
) OPERATING MENU
PROCESSINFO
PROCESS VALUES "Pressure"
Parameter name
Description
P
I
Sensor
Current
output
Pressure
Level
Flow
PRESSURE
Damping
CORRECTED
PRESS.
Position
adjust-
ment
Sensor
trim
SENSOR
PRESSURE
P
I
Sensor
Current
output
Pressure
Level
Flow
PRESSURE
Damping
CORRECTED
PRESS.
Position
adjust-
ment
Sensor
trim
SENSOR
PRESSURE