Description of parameters
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
76
Hauser
HEIGHT UNIT (708)
Selection
Select level unit.
Prerequisite:
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry
Options:
• mm
• dm
• cm
• m
• inch
• ft
• User unit,
see also the following parameter description for CUSTOMER UNIT H
and CUST. UNIT FACT. H.
Factory setting:
m
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
See also CUST. UNIT FACT. H.
Prerequisite:
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
See also CUSTOMER UNIT H.
Prerequisite:
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE = 0.5 m (1.6 ft)
i
1 PU
– Entry CUSTOMER UNIT H: PU
– Entry CUST. UNIT FACT. H: 2
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
TANK HEIGHT (859)
Entry
Enter tank height.
Prerequisite:
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Factory setting:
1.0 m
Table 11: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description