Flow measurement
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
40
Hauser
6
Flow measurement
6.1
Calibration
Example:
In this example, a volume flow should be measured in m
3
/s.
!
Note!
• The "Flow measurement" measuring mode is only available for the Deltabar S differential pressure
transmitter.
• See also Operating Instructions BA00270P Deltabar S, Section 6.4 "Flow measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 91 ff, Table 12: BASIC SETUP
– Page 98 ff, Table 15: EXTENDED SETUP.
• For a description of further parameters, see
– Page 98, Table 15: EXTENDED SETUP
– Page 123, Table 29: PROCESS VALUES.
#
Warning!
If the measuring mode is changed, the span setting (URV) must be verified in the "Calibration"
"Basic Setup" operating menu and, if necessary, reconfigured.