Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
57
SET URV (246)
Entry
Set upper range value – without reference pressure.
Enter pressure value for the upper current value (20 mA).
Factory setting:
High sensor limit (
See PRESS. SENS HILIM, Page 119)
GET LRV (309)
Entry
Set lower range value – reference pressure is present at device.
The pressure for the lower current value (4 mA) is present at device. With the "Confirm"
option, you assign the lower current value to the pressure value present.
On-site display: the pressure value present is displayed in the bottom line.
Options:
• Abort
• Confirm
GET URV (310)
Entry
Set upper range value – reference pressure is present at device.
The pressure for the upper current value (20 mA) is present at device. With the "Confirm"
option, you assign the upper current value to the pressure value present.
On-site display: the pressure value present is displayed in the bottom line.
Options:
• Abort
• Confirm
DAMPING VALUE (247)
Entry
Enter damping time (time constant
).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 7: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Pressure"
Parameter name
Description