Trouble-shooting
Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
134
Hauser
604 (W604)
Warning
C
Funktion
check (C)
C>Linearisation table not valid.
Less than 2 points or points too
close
!
Note!
From software version "02.10.xx" onwards, there is no min. span for the
Y-points.
– The linearisation table consists of
less than 2 points.
– Add to linearisation table. If
necessary, perform linearisation
again.
58
– At least 2 points in the
linearisation table are too close
together. A minimum gap of 0.5
% of the distance between two
points must be maintained.
Spans for the "Pressure
linearized" option: HYDR. PRESS
MAX. – HYDR. PRESS MIN.;
TANK CONTENT MAX. – TANK
CONTENT MIN.
Spans for the "Height linearized"
option: LEVEL MAX – LEVEL
MIN; TANK CONTENT MAX. –
TANK CONTENT MIN.
– Correct linearisation table and
accept again.
613 (W613)
Warning
I
Funktion
check (C)
I>Simulation is active
– Simulation is switched on, i.e.
the device is not measuring at
present.
– Switch off simulation.
60
620 (E620)
Error
C
Factory
setting:
Warning C
Out of
specification
(S)
C>Current output out of range
The current is outside the permitted
range 3.8 to 20.5 mA.
– The pressure applied is outside
the set measuring range (but
within the sensor range).
– Check pressure applied,
reconfigure measuring range if
necessary (
See also these
Operating Instructions, chapter 4
to 6.)
– Perform reset (Code 7864) and
carry out calibration again.
49
– Loose connection at sensor cable
– Wait a short period of time and
tighten the connection, or avoid
loose connection.
700 (W700)
Warning
C
Maintenance
request (M)
C>Last configuration not
stored
– An error occurred when writing
or reading configuration data or
the power supply was
disconnected.
– Perform reset (Code 7864) and
carry out calibration again.
54
– Main electronics defect.
– Replace main electronics.
701 (W701)
Warning
C
Funktion
check (C)
C>Measuring chain config.
exceeds sensor range
– The calibration carried out would
result in the sensor nominal
operating range being undershot
or overshot.
– Carry out calibration again.
50
702 (W702)
Warning
C
Maintenance
request (M)
C>HistoROM data not
consistent.
– Data were not written correctly
to the HistoROM, e.g. if the
HistoROM was detached during
the writing process.
– Repeat upload.
– Perform reset (Code 7864) and
carry out calibration again.
55
– HistoROM does not have any
data.
– Copy suitable data to the
HistoROM. (
See also
Operating Instructions
BA00270P (Deltabar S),
BA00271P (Cerabar S) or
BA00332P (Deltapilot S), Section
5.5.1 "Copying configuration
data".)
703 (A703)
Alarm
B
Failure (F)
B>Measurement error
– Fault in the main electronics.
– Briefly disconnect device from
the power supply.
22
– Main electronics defect.
– Replace main electronics.
Code
Error type/
NA 64
Corresponds
NE 107
Message/description
Cause
Measure
Prio
rity