Cerabar S/Deltabar S/Deltapilot S 4...20mA HART
Description of parameters
Hauser
83
Table 13: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
The following parameters are displayed if you selected the "Height Linearized" option for the LEVEL MODE parameter.
Select this level type if you require two measured variables or if the container shape is given with value pairs, e.g. height
and volume.
The following combinations are possible:
• Volume
• Mass
• %
• %-Height + Volume
• %-Height + Mass
• %-Height + %
The 1st measured variable (%-Height or Height) must be in direct proportion to the measured pressure. The 2nd
measured variable (Volume, Mass or %) must not be in direct proportion. A linearisation table must be entered for the
2nd measured variable. The 2nd measured variable is assigned to the 1st measured variable by means of this table.
Prerequisite
:
• MEASURING MODE = Level (
see also Page 45).
• LEVEL SELECTION = Level Standard (
see also Page 46).
• LEVEL MODE = Height Linearized (
see also Page 68).
Note:
See also
– Page 67 ff, Table 10: BASIC SETUP – general
– Page 96 ff, Table 16: EXTENDED SETUP
– Page 100 ff, Table 18: LINEARISATION – on-site operation
– Page 104 ff, Table 19: LINEARISATION – Digital communication
– Page 122 ff, Table 28: PROCESS VALUES
– Page 14 ff, Section 5 "Level measurement".
COMB. MEASURAND (806)
Selection
Select measured variable.
Options:
• Height and Volume
• Height and Mass
• Height and %
• %-Height and Volume
• %-Height and Mass
• %-Height and %
Factory setting:
%-Height and %
HEIGHT UNIT (708)
Selection
Select level unit for the 1st measured variable.
Prerequisite:
• COMB. MEASURAND = Height and Volume, Height and Mass or Height and %
Options:
• mm
• dm
• cm
• m
• inch
• ft
• User unit,
see also the following parameter description for CUSTOMER UNIT H
and CUST. UNIT FACT. H.
Factory setting:
m