Chapter 4 Wiring and Introduction
EMSD5 AC Servo Manual
36
Fig.4-19 Single Point Grounding Diagram
⚫
The ground handling of a noise filter installed in the control cabinet.
When the noise filter and servo driver are installed in the same control cabinet, it is
recommended that the filter and servo driver are fixed on the same metal plate. To ensure
the contact part is conductive and lapped well, and the metal plate is grounded.
Fig.4-20 Ground Connection Handling Of Noise Filter