Modbus Commands
9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name
Address
Data
Type
Client
Access
Description
Modicon
Daniel
Control.Calibration.Span_5
2010
2010
Boolean R/W
Span calibration comp5 (1=start)
Control.Calibration.Span_All
2022
2022
Boolean R/W
Span calibration all (1=start)
Control.Calibration.Zero_1
2001
2001
Boolean R/W
Zero calibration comp1 (1=start)
Control.Calibration.Zero_2
2002
2002
Boolean R/W
Zero calibration comp2 (1=start)
Control.Calibration.Zero_3
2003
2003
Boolean R/W
Zero calibration comp3 (1=start)
Control.Calibration.Zero_4
2004
2004
Boolean R/W
Zero calibration comp4 (1=start)
Control.Calibration.Zero_5
2005
2005
Boolean R/W
Zero calibration comp5 (1=start)
Control.Calibration.Zero_All
2021
2021
Boolean R/W
Zero calibration all (1=start)
Control.Calibration.ZeroSpan_1
2011
2011
Boolean R/W
Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_2
2012
2012
Boolean R/W
Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_3
2013
2013
Boolean R/W
Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_4
2014
2014
Boolean R/W
Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_5
2015
2015
Boolean R/W
Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_All
2023
2023
Boolean R/W
Zero+span calibration all (1=start)
Control.Range.CurrentRange1
3451
3451
Word
R/W
current range comp1 (0=R1, 1=R2,
2=R3, 3=R4)
Control.Range.CurrentRange2
3452
3452
Word
R/W
current range comp2 (0=R1, 1=R2,
2=R3, 3=R4)
Control.Range.CurrentRange3
3453
3453
Word
R/W
current range comp3 (0=R1, 1=R2,
2=R3, 3=R4)
Control.Range.CurrentRange4
3454
3454
Word
R/W
current range comp4 (0=R1, 1=R2,
2=R3, 3=R4)
Control.Range.CurrentRange5
3455
3455
Word
R/W
current range comp5 (0=R1, 1=R2,
2=R3, 3=R4)
Info.InterfaceID
4033
4033
Word
RO
ID of used Interface(1=SerProc
2=SerSvc 17=ETH1 18=ETH2)
Info.ProgramVersion
4011…
4016
4011…
4016
String
RO
software release version
Info.SensorVersion
4026
4026
Word
RO
Version number of sensor firmware
Info.SerialNumber
3141…
3147
3141…
3147
String
RO
serial number of the device
PV1
6001…
6002
9001
Float
RO
Primary Variable 1
PV2
6003…
6004
9002
Float
RO
Primary Variable 2
PV3
6005…
6006
9003
Float
RO
Primary Variable 3
PV4
6007…
6008
9004
Float
RO
Primary Variable 4
PV5
6009…
6010
9005
Float
RO
Primary Variable 5
Service.Calibration.ChanProcMode1
3311
3311
Word
R/W
cal proc mode comp1 (0=Disabled
1=Manual 2=SingleAuto 3=AdvCal)
Service.Calibration.ChanProcMode2
3312
3312
Word
R/W
cal proc mode comp2 (0=Disabled
1=Manual 2=SingleAuto 3=AdvCal)