6.6
Create archives manually
There are three major differences between manually created archives and automatically
created archives:
•
Manual archives only include information already in the CSI 2600. Automatically-
generated archives can include information which is received after the transient
collection predicate = TRUE.
•
Manual archives do not automatically have a date-time stamp appended to them.
Ensure that unique names are assigned.
•
Manual archives may have more than one hour of measurements in them.
Automatically generated archives have a maximum of 60 minutes of
measurements.
Procedure
1.
In Online Watch, select a component that has transient signals.
2.
Right-click and select
Start Transient Archive
.
3.
Define the manual archive characteristics.
Postrequisites
Observe the progress of manual archives in the Transient Archive Status tab.
6.7
Disable archive predicates
An analyst can disable the creation of automatic archives during startup or when the
machine is being cycled and multiple archives are not desired.
Procedure
1.
In the Transient Status tab, right-click on the archive predicate and select
Disable
Archive Predicate
.
A caution window appears.
2.
Click
Okay
to confirm disabling.
The predicate State on the Transient Status tab reads
Disabled
.
To re-enable the archive, right-click on the archive predicate and select
Enable Archive
Predicate
.
Example: Archive creation
When an archive predicate changes from
DISABLED
to
TRUE
, no archive is created.
Consider the following sequence:
1.
Archive predicate is false.
2.
Archive predicate is disabled prior to machinery start-up.
Data collection and analysis
70
MHM-97453, Rev 1
Summary of Contents for Machinery Health Expert CSI 2600
Page 1: ...User Guide MHM 97453 Rev 1 April 2014 CSI 2600 Machinery Health Expert User Guide ...
Page 8: ...CSI 2600 back view Figure 2 2 Introduction to the CSI 2600 4 MHM 97453 Rev 1 ...
Page 12: ...Introduction to the CSI 2600 8 MHM 97453 Rev 1 ...
Page 26: ...Getting started 22 MHM 97453 Rev 1 ...
Page 64: ...Software configuration 60 MHM 97453 Rev 1 ...
Page 96: ...Data types 92 MHM 97453 Rev 1 ...
Page 100: ...D 2 Internal wiring diagram for the CSI 2600 ...
Page 106: ...Troubleshooting 102 MHM 97453 Rev 1 ...
Page 109: ...Index MHM 97453 Rev 1 105 ...